Opportunity overview
Replacement obsolete quadrant fans in the UCV canopies & inverter drives for theatres plus filter changes. The older technology no longer supported but the Trust isn't in a position to replace the whole system. In addition before hand over the following testing is required: air velocity test at 2m and 1m above FFL inline with HTM03-01 and re-balance the four quadrants/isbursted Oil Particle(DOP) or DPC testing of the filters and frames /Entrainment test to ensure clean air zone /specialist testing required after UCV canopy modifications.
Awarded to
Amounts belong to published awards or contracts. Where several suppliers share one value, it is labelled as shared and is not a supplier-specific allocation.
MEDICAL AIR TECHNOLOGY LIMITED
- Published award value
- £40k
- Awarded
- Not supplied
- Award ID
- 1
- Status
- pending
- Location
- Manchester, UKD34, M41 7LY, United Kingdom
Classification
No classification was supplied.
Lots
- Lot 1Value not stated
Documents and notices
- Transparency notice on Find a TenderOpen source ↗